NEC Tables Reference
The lookup tables you actually reach for, on one page and free of pop-ups. Ampacity, derating factors, standard breaker ratings, conduit and box fill, and the two grounding tables — every one read from the same source our calculators use, so what you see here is what they compute.
Conductor Ampacity
Allowable ampacities of insulated conductors rated up to 2,000 V, not more than three current-carrying conductors in a raceway, cable, or earth, at an ambient of 30 °C (86 °F). Under 110.14(C) the circuit is limited by the lowest-rated termination — usually 75 °C — so the 90 °C column is a derating starting point rather than a usable answer.
| Size | Copper | Aluminum | Circular mils | ||||
|---|---|---|---|---|---|---|---|
| 60 °C | 75 °C | 90 °C | 60 °C | 75 °C | 90 °C | ||
| 14 AWG | 15 | 20 | 25 | — | — | — | 4,110 |
| 12 AWG | 20 | 25 | 30 | 15 | 20 | 25 | 6,530 |
| 10 AWG | 30 | 35 | 40 | 25 | 30 | 35 | 10,380 |
| 8 AWG | 40 | 50 | 55 | 35 | 40 | 45 | 16,510 |
| 6 AWG | 55 | 65 | 75 | 40 | 50 | 55 | 26,240 |
| 4 AWG | 70 | 85 | 95 | 55 | 65 | 75 | 41,740 |
| 3 AWG | 85 | 100 | 115 | 65 | 75 | 85 | 52,620 |
| 2 AWG | 95 | 115 | 130 | 75 | 90 | 100 | 66,360 |
| 1 AWG | 110 | 130 | 145 | 85 | 100 | 115 | 83,690 |
| 1/0 AWG | 125 | 150 | 170 | 100 | 120 | 135 | 105,600 |
| 2/0 AWG | 145 | 175 | 195 | 115 | 135 | 150 | 133,100 |
| 3/0 AWG | 165 | 200 | 225 | 130 | 155 | 175 | 167,800 |
| 4/0 AWG | 195 | 230 | 260 | 150 | 180 | 205 | 211,600 |
| 250 kcmil | 215 | 255 | 290 | 170 | 205 | 230 | 250,000 |
| 300 kcmil | 240 | 285 | 320 | 195 | 230 | 260 | 300,000 |
| 350 kcmil | 260 | 310 | 350 | 210 | 250 | 280 | 350,000 |
| 400 kcmil | 280 | 335 | 380 | 225 | 270 | 305 | 400,000 |
| 500 kcmil | 320 | 380 | 430 | 260 | 310 | 350 | 500,000 |
| 600 kcmil | 350 | 420 | 475 | 285 | 340 | 385 | 600,000 |
240.4(D) caps small conductors below these figures: 15 A for 14 AWG copper, 20 A for 12 AWG, 30 A for 10 AWG — and 15 A for 12 AWG aluminum, 25 A for 10 AWG. That is why 12 AWG copper reads 25 A here and still sits on a 20-amp breaker.
Dwelling Services & Feeders
For a dwelling service, or a feeder carrying the entire load of a one-family dwelling, conductors may be sized at 83% of the rating. This does not reach an ordinary subpanel feeder — that sizes from Table 310.16 above.
| Service or feeder rating | Copper | Aluminum / copper-clad | 83% of rating |
|---|---|---|---|
| 100 A | 4 AWG | 2 AWG | 83.0 A |
| 110 A | 3 AWG | 1 AWG | 91.3 A |
| 125 A | 2 AWG | 1/0 AWG | 103.8 A |
| 150 A | 1 AWG | 2/0 AWG | 124.5 A |
| 175 A | 1/0 AWG | 3/0 AWG | 145.3 A |
| 200 A | 2/0 AWG | 4/0 AWG | 166.0 A |
| 225 A | 3/0 AWG | 250 kcmil | 186.8 A |
| 250 A | 4/0 AWG | 300 kcmil | 207.5 A |
| 300 A | 250 kcmil | 350 kcmil | 249.0 A |
| 350 A | 350 kcmil | 500 kcmil | 290.5 A |
| 400 A | 400 kcmil | 600 kcmil | 332.0 A |
Derating Factors
Both factors are applied to the ampacity from the conductor's insulation temperature column — normally 90 °C — and the result is then checked against the 75 °C termination limit. Starting from the 90 °C column is often what saves a conductor size.
Ambient temperature correction
310.15(B)(1) — base ambient 30 °C
| Ambient | 60 °C | 75 °C | 90 °C |
|---|---|---|---|
| ≤ 10 °C (50 °F) | 1.29 | 1.20 | 1.15 |
| 11–15 °C (52–59 °F) | 1.22 | 1.15 | 1.12 |
| 16–20 °C (61–68 °F) | 1.15 | 1.11 | 1.08 |
| 21–25 °C (70–77 °F) | 1.08 | 1.05 | 1.04 |
| 26–30 °C (79–86 °F) | 1.00 | 1.00 | 1.00 |
| 31–35 °C (88–95 °F) | 0.91 | 0.94 | 0.96 |
| 36–40 °C (97–104 °F) | 0.82 | 0.88 | 0.91 |
| 41–45 °C (106–113 °F) | 0.71 | 0.82 | 0.87 |
| 46–50 °C (115–122 °F) | 0.58 | 0.75 | 0.82 |
| 51–55 °C (124–131 °F) | 0.41 | 0.67 | 0.76 |
| 56–60 °C (133–140 °F) | — | 0.58 | 0.71 |
| 61–70 °C (142–158 °F) | — | 0.33 | 0.58 |
| 71–80 °C (160–176 °F) | — | — | 0.41 |
Conductor bundling adjustment
310.15(C)(1) — current-carrying conductors only
| Conductors in the raceway | Factor |
|---|---|
| 1–3 conductors | 1.00 |
| 4–6 conductors | 0.80 |
| 7–9 conductors | 0.70 |
| 10–20 conductors | 0.50 |
| 21–30 conductors | 0.45 |
| 31–40 conductors | 0.40 |
| 41 or more conductors | 0.35 |
Equipment grounding conductors never count. A neutral counts where it carries current. A nipple no longer than 24 in is exempt under Chapter 9, Table 1, Note 4.
Standard OCPD Ratings
The only ratings fuses and inverse-time breakers come in. A calculation landing between two of them rounds up — there is no 33-amp breaker.
240.6(A) also lists additional standard fuse ratings of 1, 3, 6, 10 and 601 A and above, rarely seen on branch circuits.
Conduit Fill
Three tables working together: Table 1 gives the allowable percentage by conductor count, Table 4 the raceway's internal area, and Table 5 each conductor's area including insulation.
Table 1 — maximum percent fill
1 conductor
53%
2 conductors
31%
3 or more
40%
Two conductors is stricter than three — that is the code, not a typo, and it means the maximum count cannot be found by a single division. A nipple of 24 in or less goes to 60% under Note 4, and the 310.15(C)(1) adjustment factors do not apply to it.
Table 4 — raceway internal area, in²
Total (100%) area by type and trade size
| Trade size | EMT | PVC Sch 40 | PVC Sch 80 | RMC | IMC |
|---|---|---|---|---|---|
| 1/2" | 0.304 | 0.285 | 0.217 | 0.314 | 0.342 |
| 3/4" | 0.533 | 0.508 | 0.409 | 0.549 | 0.586 |
| 1" | 0.864 | 0.832 | 0.688 | 0.887 | 0.959 |
| 1-1/4" | 1.496 | 1.453 | 1.237 | 1.526 | 1.647 |
| 1-1/2" | 2.036 | 1.986 | 1.711 | 2.071 | 2.225 |
| 2" | 3.356 | 3.291 | 2.874 | 3.408 | 3.630 |
| 2-1/2" | 5.858 | 4.695 | 4.119 | 4.866 | 5.135 |
| 3" | 8.846 | 7.268 | 6.442 | 7.499 | 7.922 |
| 4" | 14.753 | 12.554 | 11.258 | 12.882 | 13.457 |
Table 5 — conductor area, in²
Including insulation
| Size | THHN / THWN-2 | XHHW-2 |
|---|---|---|
| 1 AWG | 0.1562 | 0.1534 |
| 2 AWG | 0.1158 | 0.1146 |
| 3 AWG | 0.0973 | 0.0962 |
| 4 AWG | 0.0824 | 0.0814 |
| 6 AWG | 0.0507 | 0.0590 |
| 8 AWG | 0.0366 | 0.0437 |
| 10 AWG | 0.0211 | 0.0243 |
| 12 AWG | 0.0133 | 0.0181 |
| 14 AWG | 0.0097 | 0.0139 |
| 1/0 AWG | 0.1855 | 0.1825 |
| 2/0 AWG | 0.2223 | 0.2190 |
| 3/0 AWG | 0.2679 | 0.2642 |
| 4/0 AWG | 0.3237 | 0.3197 |
| 250 kcmil | 0.3970 | 0.3904 |
| 350 kcmil | 0.5242 | 0.5153 |
| 500 kcmil | 0.7073 | 0.6984 |
Note 7 permits rounding up where a calculation for conductors all of the same size produces a decimal of 0.8 or larger. Annex C bakes that in, which is why a pre-computed Annex C count can read one higher than a strict area calculation. Our conduit fill calculator computes strictly, so it is conservative by one at those boundaries.
Box Fill
Each conductor entering and terminating counts once. All internal cable clamps together count as one, at the largest conductor present. Each device yoke counts as two. All equipment grounding conductors together count as one. A conductor that both begins and ends inside the box — a pigtail — counts zero.
314.16(B) — volume per conductor
| Conductor size | Free space required |
|---|---|
| 6 AWG | 5.00 in³ |
| 8 AWG | 3.00 in³ |
| 10 AWG | 2.50 in³ |
| 12 AWG | 2.25 in³ |
| 14 AWG | 2.00 in³ |
| 16 AWG | 1.75 in³ |
| 18 AWG | 1.50 in³ |
Common box volumes
Table 314.16(A) plus trade sizes
| Box | Volume |
|---|---|
| 3" × 2" × 2" device box | 10.0 in³ |
| 3" × 2" × 2-1/4" device box | 10.5 in³ |
| 3" × 2" × 2-1/2" device box | 12.5 in³ |
| 3" × 2" × 2-3/4" device box | 14.0 in³ |
| 3" × 2" × 3-1/2" device box | 18.0 in³ |
| Single-gang plastic box, 20.3 in³ | 20.3 in³ |
| Single-gang plastic box, 22.5 in³ | 22.5 in³ |
| 4" square × 1-1/2" box | 21.0 in³ |
| 4" square × 2-1/8" box | 30.3 in³ |
| 4-11/16" square × 1-1/2" box | 29.5 in³ |
| 4-11/16" square × 2-1/8" box | 42.0 in³ |
Grounding Conductors
Two different conductors from two different tables. The equipment grounding conductor is keyed to the overcurrent device; the grounding electrode conductor is keyed to the largest ungrounded service-entrance conductor, then capped by which electrode it lands on.
Table 250.122 — equipment grounding conductor
By OCPD rating. Note there is no 30 A row.
| OCPD up to | Copper | Aluminum |
|---|---|---|
| 15 A | 14 AWG | 12 AWG |
| 20 A | 12 AWG | 10 AWG |
| 60 A | 10 AWG | 8 AWG |
| 100 A | 8 AWG | 6 AWG |
| 200 A | 6 AWG | 4 AWG |
| 300 A | 4 AWG | 2 AWG |
| 400 A | 3 AWG | 1 AWG |
| 500 A | 2 AWG | 1/0 AWG |
| 600 A | 1 AWG | 2/0 AWG |
| 800 A | 1/0 AWG | 3/0 AWG |
| 1000 A | 2/0 AWG | 4/0 AWG |
| 1200 A | 3/0 AWG | 250 kcmil |
Table 250.66 — grounding electrode conductor
By largest service-entrance conductor
| Copper service | Aluminum service | Cu GEC | Al GEC |
|---|---|---|---|
| 2 AWG or smaller | 1/0 AWG or smaller | 8 AWG | 6 AWG |
| 1 or 1/0 AWG | 2/0 or 3/0 AWG | 6 AWG | 4 AWG |
| 2/0 or 3/0 AWG | 4/0 AWG or 250 kcmil | 4 AWG | 2 AWG |
| over 3/0 through 350 kcmil | over 250 through 500 kcmil | 2 AWG | 1/0 AWG |
| over 350 through 600 kcmil | over 500 through 900 kcmil | 1/0 AWG | 3/0 AWG |
| over 600 through 1100 kcmil | over 900 through 1750 kcmil | 2/0 AWG | 4/0 AWG |
| over 1100 kcmil | over 1750 kcmil | 3/0 AWG | 250 kcmil |
Then the caps: to a rod, pipe or plate the GEC need not exceed 6 AWG copper (250.66(A)); to a concrete-encased electrode, 4 AWG (250.66(B)); to a ground ring, no larger than the ring itself (250.66(C)). A metal water pipe has no cap.
Sources & standards: all tables are reproduced from NEC (NFPA 70) 2023 — Table 310.16, Table 310.12, 310.15(B)(1), 310.15(C)(1), 240.4(D), 240.6(A), Chapter 9 Tables 1, 4, 5 and 8 with Notes 4 and 7, Annex C, 314.16 and Table 314.16(A), Table 250.66 with 250.66(A)–(C), and Table 250.122. Baseline is NEC 2023; most states are on the 2020 or 2023 cycle, and NEC 2026 was published in 2025. These are planning aids — local amendments override the model code, and a licensed electrician plus the AHJ have final say on anything installed.
Let the calculator do the lookup
Every table on this page is read by one of our free calculators — same numbers, none of the cross-referencing.
Browse all electrical calculators →