Electrical Tools · NEC 2023 · Free

Voltage Drop Calculator — The 3% Rule, Properly

Voltage drop in volts and percent for any gauge, length, and load — plus the longest run that still lands inside the 3% recommendation. Every conductor has resistance, so every run gives up some voltage on the way to the load. This calculator returns the drop in volts and percent, the voltage that actually arrives, and the longest one-way run that keeps you inside your limit — for single-phase and three-phase, copper and aluminum, 120 V through 480 V.

Worth knowing: the 3% and 5% figures are Informational Notes in NEC 210.19(A) and 215.2(A) — explanatory guidance, not enforceable Code. Most specifications and many local amendments adopt them anyway, and a few articles (647.4(D), 695.7) do set hard limits. Treat 3% as the professional default.

Check the drop on your run

amps
5400 A
ft

Voltage drop

2.05%

Within the 3% recommendation.

Volts dropped

4.92 V

Volts at the load

235.1 V

See the breakdown
K (resistivity)
Circular mils
Phase multiplier
Against the limit
Max compliant run

Uses the circular-mils approximation, which ignores conductor reactance. For large feeders, long runs in steel raceway, or power-factor-sensitive loads, use the impedance method with Chapter 9 Table 9.

The formula, explained in plain English

Voltage drop is Ohm's law applied to the wire itself. Current through the conductor's own resistance produces a voltage that never reaches the load.

# Single-phase
VD = 2 × K × I × L ÷ CM
# Three-phase (balanced)
VD = 1.732 × K × I × L ÷ CM
# As a percentage
VD% = VD ÷ Vsystem × 100  ·  Vload = Vsystem − VD
# Longest compliant one-way run
Lmax = limit% × V × CM ÷ (multiplier × K × I)
# Where
K = 12.9 copper, 21.2 aluminum · I = load amps · L = one-way feet · CM = circular mils

One-way length, doubled

Enter the distance from panel to load, not the total conductor length. The formula's multiplier already accounts for the return path — entering round-trip footage doubles the answer.

Volts are absolute, percent is relative

The volts dropped don't change with system voltage. Only the percentage does. That single fact explains why 240 V and 480 V distribution exist.

Why aluminum drops more

K = 21.2 versus copper's 12.9 means about 64% more drop at the same gauge — which is why aluminum feeders are typically run two sizes larger than their copper equivalent.

What this method ignores

Reactance. For conductors above about 1/0 in steel raceway, or loads with poor power factor, the impedance method using Chapter 9 Table 9 gives a more accurate answer.

Worked examples

A pass, a bad fail, and the case that shows why voltage matters more than gauge on long runs.

1

Garage subpanel feeder — 6 AWG, 50 A, 100 ft

Copper · 240 V single-phase · 3% limit. The defaults above.

VD = 2 × 12.9 × 50 × 100 ÷ 26,240 = 4.92 V
VD% = 4.92 ÷ 240 × 100 = 2.05%
V at load = 240 − 4.92 = 235.1 V
PASS · max compliant run = 146 ft

Result: comfortable at 2.05%, with 46 feet of headroom before the run would need 4 AWG.

2

Shed circuit — 12 AWG, 20 A, 150 ft at 120 V

Copper · 120 V single-phase · 3% limit.

VD = 2 × 12.9 × 20 × 150 ÷ 6,530 = 11.85 V
VD% = 11.85 ÷ 120 × 100 = 9.88%
V at load = 108.1 V
FAIL · max compliant run = 45 ft

Result: 108 volts at the load will make motors buzz and struggle to start. The fix is 6 AWG, or feeding the shed at 240 V with a small subpanel.

3

Three-phase machine feed — 4/0, 100 A, 400 ft at 480 V

Copper · 480 V three-phase · 3% limit.

VD = 1.732 × 12.9 × 100 × 400 ÷ 211,600 = 4.22 V
VD% = 4.22 ÷ 480 × 100 = 0.88%
PASS easily

Result: under 1% across 400 feet. The same 100 A load at 120 V single-phase on the same conductor drops 4.88 V — which is 4.06%, more than four times the percentage on identical copper. Higher voltage and three-phase working together is what makes long industrial feeders practical.

Maximum run length at 3% — 240 V copper

Longest one-way run in feet before drop passes 3%, single-phase at 240 V. Blank cells are combinations where Table 310.16 or the 240.4(D) small-conductor rule will not permit that current on that conductor at all. At 120 V, halve every number.

Conductor 15 A20 A30 A50 A100 A
14 AWG 76 ft
12 AWG 121 ft91 ft
10 AWG 193 ft144 ft96 ft
8 AWG 307 ft230 ft153 ft92 ft
6 AWG 488 ft366 ft244 ft146 ft
4 AWG 776 ft582 ft388 ft232 ft
3 AWG 979 ft734 ft489 ft293 ft146 ft
2 AWG 1234 ft925 ft617 ft370 ft185 ft
1/0 AWG 1964 ft1473 ft982 ft589 ft294 ft
4/0 AWG 3936 ft2952 ft1968 ft1181 ft590 ft

Sources & standards: NEC (NFPA 70) 2023 — 210.19(A) and 215.2(A) Informational Notes on voltage drop, 90.5(C) on the status of Informational Notes, Chapter 9 Table 8 conductor properties, Chapter 9 Table 9 for the impedance method, Table 310.16 ampacities, 240.4(D) small-conductor protection. Local amendments override the model code.

Frequently asked questions

Common questions about voltage drop, the 3% rule, and long runs.

Is 3% voltage drop a code requirement or a recommendation?

A recommendation. The 3% branch-circuit and 5% combined feeder-plus-branch figures appear in Informational Notes to NEC 210.19(A) and 215.2(A), and Article 90.5(C) states that Informational Notes are explanatory and not enforceable as Code requirements. That said, many project specifications, engineering standards, and local amendments adopt them as mandatory — and some specific articles (like 647.4(D) for sensitive electronic equipment, or 695.7 for fire pumps) do impose hard voltage-drop limits. Treat 3% as the professional default, not as optional.

Why 2× for single-phase and 1.732× for three-phase?

Single-phase current flows out on the hot and back on the neutral, so it travels the run length twice — hence the factor of 2. In a balanced three-phase circuit the three phase currents are 120° apart and partly cancel in the return path, which works out to a factor of √3 ≈ 1.732 rather than 2. That is a big part of why three-phase distribution wins on long runs.

What is an acceptable voltage drop?

Aim for 3% or less on a branch circuit and 5% or less for the feeder and branch circuit combined. Motors are particularly sensitive: low voltage raises current draw, which raises heat and shortens winding life. Resistive loads like water heaters simply run slower and cost more per unit of output. LED drivers and electronics usually tolerate more drop but can flicker or reset near the limit.

Does voltage drop matter more on 120 V than 240 V?

Yes, dramatically. Drop in volts depends only on current, length, and conductor size — not on system voltage. But drop as a percentage is that figure divided by the system voltage. The same 6-volt drop is 5% at 120 V and only 2.5% at 240 V. That is why long outbuilding runs are almost always fed at 240 V and why commercial work uses 480 V.

How far can I run 12 AWG on a 20 amp circuit?

At 240 V single-phase, about 91 feet before 12 AWG copper passes 3%. At 120 V it is only about 45 feet at the full 20 A load. If the actual load is lower than the breaker rating, the compliant run gets longer in proportion — drop scales with current, not with breaker size. Enter your real load current above rather than the breaker rating.

Does upsizing wire for voltage drop change my ground wire size?

Yes. NEC 250.122(B) requires the equipment grounding conductor to be increased proportionally when the ungrounded conductors are upsized — including when the reason is voltage drop. The ratio is by circular mils. The Ground Wire Size Calculator has a toggle that does this proportional upsize for you.

Should I use the load current or the breaker rating?

Use the actual load current. Voltage drop is a function of the current that really flows, so sizing to a breaker rating the circuit never reaches over-builds the conductor. The exception is a circuit you expect to load to capacity — an EV charger or an electric water heater running at nameplate — where load and rating are effectively the same number.

Drop within limits? Price the run in seconds.

Knowing the conductor is one thing; pricing the pull, the terminations, and the labor is another. Describe the job or upload photos and TradesQuote's AI builds a detailed line-item estimate — quantities, unit prices, and totals — validated by a built-in quality control agent.

AI line-item estimates

Quantities, unit prices, and totals generated instantly.

Knowledge base

Upload past jobs so estimates reflect your real pricing.

Shareable & signable

Clients review, accept, and sign from a public link.

No credit card required · 14-day free trial · Cancel anytime

More electrical calculators