Electrical Tools · Free

Range & Dryer Demand — Tables 220.55 and 220.54

A 12 kW range counts as 8 kW. Column C is a demand in kilowatts, not a percentage — the most misread table in Article 220. And every dryer has a 5,000 VA floor no matter how small its nameplate.

Enter the appliances

Household ranges — Table 220.55

Electric clothes dryers — Table 220.54

Both tables cover dwelling units only. A commercial kitchen uses 220.56 instead. A cooktop and up to two wall ovens on one circuit in the same room may be added together and treated as a single range under Note 4.

Combined demand load

13,000 VA

Ranges

8.00 kW

Dryers

5,000 VA

Connected

17,000 VA

Removed

24%

See the breakdown
Ranges connected
Column C
Note 1
Note 3 alternative
Dryer each
Dryers connected
Table 220.54
Combined

Column C is a demand in kilowatts, not a percentage.

The method, explained in plain English

# Ranges — Table 220.55
1 range, 1¾ to 12 kW → 8 kW flat (Column C)
over 12 kW → 8 kW × (1 + 5% per kW over 12) Note 1
under 8¾ kW → Column A or B percentage instead Note 3
# Dryers — Table 220.54
each = max(5,000 VA, nameplate)
1–4 @ 100% · 5 @ 85% · 6 @ 75% · 10 @ 50%
# These belong to the Part III standard method only
220.82 takes nameplates at full value instead

Kilowatts, not percent

Column C's numbers are demands. Reading 8 as "80%" of a 12 kW range gives 9.6 kW and is wrong — the correct answer is 8 kW flat.

The dryer has a floor, not a factor

In a single dwelling 220.54's demand factor is 100%. What changes the number is the 5,000 VA minimum, which raises small dryers rather than lowering big ones.

Note 1 multiplies the table

The 5%-per-kilowatt increase applies to the 8 kW Column C figure, not to the appliance nameplate. A 16 kW range is 9.6 kW, not 19.2.

Never stack with 220.82

The optional method has its own diversity in the 40% remainder factor. Applying a range demand factor first double-counts it and undersizes the service.

Worked examples

One house, one big range, and one apartment building.

1

One house — the defaults

A single 12 kW range and a single 5 kW dryer.

range: 12 kW connected → Column C → 8,000 VA
dryer: max(5,000, 5,000) × 100% = 5,000 VA
combined 13,000 VA against 17,000 connected — 24% removed

Result: four kilowatts of the calculation disappear on the range alone. That is roughly 17 A on a 240 V service — the difference between comfortably inside a 100 A service and not.

2

A 16 kW professional range — Note 1

Same house, a much larger range.

16 kW is 4 kW over 12 → 4 × 5% = 20%
8 kW × 1.20 = 9.6 kW
a third more range, 1.6 kW more calculated load

Result: upgrading from a 12 kW to a 16 kW range adds under 7 A to the service calculation. Homeowners routinely assume a bigger range forces a service upgrade; the table says otherwise.

3

Ten apartments — where the tables really earn their keep

Ten 12 kW ranges and ten 5 kW dryers on one service.

ranges: 120 kW connected → Column C row 10 → 25 kW
dryers: 50 kW connected × 50% → 25 kW
combined 50,000 VA against 170,000 connected — 71% removed

Result: both tables land on exactly 25 kW at ten units, by coincidence rather than design. Without them this building's service would be sized for 170 kVA of cooking and laundry that will never happen at once.

How both tables scale with unit count

Ranges at 12 kW each, dryers at 5 kW each. Notice the ranges fall away far faster at low counts, while the dryers hold at 100% until the fifth unit.

Units Ranges connected Range demand Of connected Dryer demand Factor
1 12 kW 8.00 kW 67% 5.0 kW 100%
2 24 kW 11.00 kW 46% 10.0 kW 100%
4 48 kW 17.00 kW 35% 20.0 kW 100%
5 60 kW 20.00 kW 33% 21.3 kW 85%
6 72 kW 21.00 kW 29% 22.5 kW 75%
10 120 kW 25.00 kW 21% 25.0 kW 50%
20 240 kW 35.00 kW 15% 38.0 kW 38%
30 360 kW 45.00 kW 13% 47.3 kW 31.5%
40 480 kW 55.00 kW 11% 53.0 kW 26.5%

Sources & standards: NEC (NFPA 70) 2023 Table 220.55 for household electric ranges, wall-mounted ovens and counter-mounted cooking units over 1¾ kW, with Note 1 (the 5% per kilowatt increase above 12 kW), Note 3 (Columns A and B in lieu of Column C at 8¾ kW and below) and Note 4 (a cooktop plus up to two ovens on one circuit in the same room treated as a single range); Table 220.54 for electric clothes dryers, with the 5,000 VA minimum in 220.54 itself. Both apply to dwelling units only — commercial kitchen equipment uses 220.56. These tables belong to the Part III standard method and must not be combined with the 220.82 optional method, which applies its own diversity. Local amendments and the AHJ have final say.

Frequently asked questions

Common questions about range and dryer demand factors.

How much does a 12 kW range count as in a load calculation?

8 kW. Table 220.55 Column C gives a maximum demand of 8 kW for one household range rated over 1¾ kW through 12 kW — and that is a demand in kilowatts, not a percentage. This is the single most misread table in Article 220. A 9 kW range and a 12 kW range both count as 8 kW, so the nameplate barely matters at this size. The 8 kW figure already has diversity built into it: nobody runs every element and the oven simultaneously for long.

What about a range larger than 12 kW?

Note 1 to Table 220.55 applies: for ranges over 12 kW through 27 kW of the same rating, the Column C figure is increased by 5% for each additional kilowatt above 12. A 16 kW range is 4 kW over, so 8 kW × (1 + 20%) = 9.6 kW. Note that the 5% applies to the table value, not to the nameplate — a mistake that inflates the answer badly. Even a 27 kW commercial-style range only reaches 14 kW of demand.

How much does an electric dryer count as?

5,000 VA or the nameplate, whichever is larger, per NEC 220.54. So a 4,800 W dryer still counts as 5,000 VA, and a 5,600 W one counts as 5,600. The demand factor is 100% for one through four dryers, and only starts reducing at five: 85% at five, 75% at six, down to 50% at ten. In a single-family house there is no reduction at all — the dryer is simply its 5,000 VA floor.

Why do these demand factors exist?

Because connected load and simultaneous load are different quantities, and services are sized for the second. Ten apartments have ten ranges totalling 120 kW installed, but the probability that all ten are roasting at full output at the same moment is effectively zero. Table 220.55 counts those ten at 25 kW — an 79% reduction. Without demand factors every multifamily service in the country would be roughly four times larger than it needs to be, at enormous cost and no safety benefit.

What are Columns A and B for?

Small appliances. Column A covers cooking appliances over 1¾ kW and under 3½ kW, Column B covers 3½ kW through 8¾ kW, and both give percentages rather than kilowatts. Note 3 permits using them in lieu of Column C for appliances in those ranges — which matters because Column C's flat 8 kW would otherwise penalise a small unit. A single 6 kW wall oven is 4.8 kW under Column B against 8 kW under Column C.

Do separate cooktops and wall ovens count as one range?

Often yes, and it saves considerable load. Note 4 to Table 220.55 permits a counter-mounted cooking unit and up to two wall ovens supplied from a single branch circuit and located in the same room to be treated as a single range by adding their nameplate ratings together. A 7 kW cooktop plus a 5 kW oven totals 12 kW, which is then a single 8 kW range demand rather than two separate appliance loads.

Do these tables apply to gas ranges or commercial kitchens?

Neither. A gas range has no significant electrical cooking load — only its ignition, controls and clock, counted as an ordinary appliance. And Table 220.55 covers household equipment only; a commercial kitchen uses NEC 220.56, which is a completely different set of demand factors (100% for one or two units, then 90%, 80%, 70% and 65%) with a floor at the sum of the two largest pieces of equipment.

Does the 220.82 optional method use these tables?

No — and this catches people who work both methods on the same house. The 220.82 optional method takes appliance nameplate ratings at full value and then applies its own single reduction: the first 10 kVA at 100% and the remainder at 40%. Tables 220.55 and 220.54 belong to the Part III standard method. Applying a range demand factor and then the 40% remainder factor double-counts the diversity and understates the load.

Load calculated? Quote the work.

Service and feeder work is where estimating errors get expensive. TradesQuote turns the scope into a detailed line-item estimate — gear, conductors, terminations, and labour — validated by a built-in quality control agent.

AI line-item estimates

Quantities, unit prices, and totals generated instantly.

Knowledge base

Upload past jobs so estimates reflect your real pricing.

Shareable & signable

Clients review, accept, and sign from a public link.

No credit card required · 14-day free trial · Cancel anytime

More electrical calculators